• Full Automatic Tan Delta Tester
  • Full Automatic Tan Delta Tester
  • Full Automatic Tan Delta Tester
  • Full Automatic Tan Delta Tester
  • Full Automatic Tan Delta Tester
  • Full Automatic Tan Delta Tester

Full Automatic Tan Delta Tester

After-sales Service: 1 Year
Warranty: 1 Year
Max Diameter of Workpiece: Other
Mass Scope of Workpiece: Other
Type: Tan Delta Tester
Accuracy Grade: 0.5
Customization:
Diamond Member Since 2005

Suppliers with verified business licenses

Trading Company

Basic Info.

Model NO.
ZH
Load Way
Other
Loading Method
Other
Display
Digital
Control
Computer Control
Weight
0-100Kg
Power Source
AC220V
Oil Cylinder Position
Other
Accuracy
Accuracy: Cx: Reading X 1%+1PF
Maximum Output Current
200mA
Name
Full Automatic Tan Delta Tester
Function
Test Machine
Transport Package
Wood
Specification
28kg
Trademark
zhenhuan
Origin
China
Production Capacity
5000PCS/Year

Product Description

I. Foreword
Automatic Tan Delta Tester is a basic method in insulation test and effectively detect damp, degradation and partial defect of insulation of electrical equipment. This method is widely used in electric manufacturing, electric equipment installation, connection and preventive test. Measurement on dielectric loss of transformer, mutual inductor, reactor, capacitor, bushing and arrester is the most basic method to test their insulation property.Fully-automatic anti-interference dielectric loss tester breaks through the traditional bridge testing method and adopts variable frequency power technology, single chip and modernized electrical technology to carry out automatic frequency shift, analog-to-digital conversion and data computing. It features strong anti-interference capacity, high test speed, high precision, automatic digitization and easy operation. It adopts high-power switching power supply, which outputs 45Hz and 55Hz pure sine wave and automatically increase the voltage to a maximum value 10 KV. It can filter 50Hz interference automatically, and it is applicable to the site test of substation and other places with large electromagnetic interference.

II. Security Measures 

  1. Please read this manual carefully before using the instrument.
  2. Operator of this instrument should be equipped with the knowledge of using general electrical equipment and instrument.
  3. This instrument is suitable for both indoor and outdoor use and should be kept away from rainwater, corrosive gas, thick dust, direct sunshine and so on.
  4. The instrument should avoid severe vibration.
  5. Maintenance, care and regulation of the instrument should be conducted by professionals.  
  6. Connect the grounding terminal of the instrument with the ground by a ground wire in a reliable way before any wiring.
  7. As the testing equipment may produce HV, the testing personnel should abide by the safety operation specification strictly to prevent others from contacting high-voltage component and circuit. Personnel who are directly engaged in testing must exactly understand the high-voltage test circuit as well as key points for operation. People other than testing personnel must keep away from HV testing area and the testing area should be clearly marked with fence, rope or warning sign.
  8. Adjustment and maintenance of the instrument should be conducted in a no power-up state. Jf power-up is required, the operator must be familiar with the high-voltage hazardous components of this instrument very well.
  9. In case that the fuse is broken, replace it with another identical fuse. Any fuses of different models or direct use in short circuit is forbidden.
  10. In case that the instrument breaks down, turn the power off and check it one minute later.

III. Testable parameters

The instrument can test the following parameters and display them in figure:
Capacitance value of tested article CX is in pF or nF, 1nF=1,000pF.
Dielectric loss value of tested article tgδ is displayed with %.

IV. Performance features

1. The instrument adopts complex number current method to measure capacitance, dielectric loss and other parameters. The measured result is highly accurate and it is easy to realize automatic measurement.  
2. The instrument adopts variable frequency technology to eliminate 50Hz/60Hz power frequency interference. So a reliable data will be reachable even under the strong electromagnetic interference.  
3. The instrument adopts large screen LCD . In the process of testing, menu prompt is visualized and easy to operate.
4. The instrument is easy to operate and the measuring process is controlled by microprocessor. Once a suitable measuring method is selected, the data measurement will complete automatically under the control of microprocessor.
5. The instrument is designed to be an integrated model with reference capacitor and HV power supply in it, enables site test measurement and reduces site wiring.
6. The instrument is equipped with CVT testing function, which can achieve CVT self-exciting testing without external accessories and measure the capacitance and dielectric loss of C1 and C2 by at a time.
7. GST measurement adopts ivddv technology and avoids unstable data provided by previous GST measurement.
8. The instrument provides low voltage shell function of GST. When the bus of 220kV CVT is grounded, dielectric loss measurement can be conducted for C11 without removing 10 kV GST.
9. The instrument has a function of measuring high-voltage dielectric loss. It can carry out dielectric loss test with over 10kV with the help of voltage transformer or series resonance.
10. The instrument has a ground-fault protection function. In case that the instrument is not grounded or grounded incorrectly, the instrument will refuse to enter into normal procedure and output HV. As for the over-current protection function, it will protect the instrument from damage when the tested article is in a short circuit or breakdowns.
11. The instrument has a function of electric shock protection. When the instrument operator suffers an electric shock due to incaution, the instrument will cut off the HV immediately and thus ensure the security of operator.
 

V. Technical indicators

Accuracy: Cx: ±(reading x 1%+1pF)
tgδ: ±(reading×1%+0.00040)
Anti-interference: Variable frequency anti-interference, the above accuracy can be reached under 200% interference.
Capacitance range: Internal HV: 3pF~60000pF/10kV 60pF~1μF/0.5kV
    External HV: 3pF~1.2μF/10kV 60pF~30μF/0.5kV
               Resolution: Maximum 0.001pF, 4 valid figures.
tgδ range:unlimited, 0.001% resolution, automatic identification for capacitance, inductance and resistance of three tested articles.
Test current range: 10μA~1A
Internal HV: Set voltage range: 0.5~10kV
Maximum output current: 200mA
Buck-bust method: continuous stepless regulation
Test frequency: 45, 50, 55 single frequency
             45/55Hz automatic dual variable frequency
Frequency accuracy: ±0.01Hz
External HV: In case of UST, maximum test current is 1A, and power frequency or variable frequency is 40-70Hz
In case of GST, maximum test current is 10kV/1A, and power frequency or variable frequency is 40-70Hz
CVT self-exciting low voltage output: Output voltage 3~50V, output current 3~30A
Measuring duration: About 40s, depending on measuring method
Input power supply: 180V~270VAC, 50Hz/60Hz±1%, supplied by alternating current or generator
Computer interface: Standard RS232 interface
Printer: mini-type thermal printer
Environment temperature: -10ºC~50ºC
Relative humidity: <90%
Overall dimension:460×360×350mm
Weight:28kg
Full Automatic Tan Delta TesterFull Automatic Tan Delta TesterFull Automatic Tan Delta TesterFull Automatic Tan Delta Tester

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now